Guide
What size breaker for a tankless water heater?
The kilowatt rating sets the amps; the manual sets the breakers.
Short answer
Use the breakers in the installation manual. Whole-house electric tankless heaters split their load across two to four 240 V circuits, each on a 40 or 50 A double-pole breaker. Rheem’s 18 kW RTEX-18 draws 75 A and takes 2 × 40 A breakers; a 36 kW unit draws 150 A and takes 4 × 40 A (RTEX-36) or 3 × 50 A (Stiebel Eltron Tempra 36). For the total amps, divide the watts by 240.
Breakers by model
| Model | kW | Total amps | Circuits | Amps per circuit | Breaker each | Copper wire |
|---|---|---|---|---|---|---|
| Rheem RTEX-18 | 18 | 75.0 | 2 | 37.5 | 40 A | 8 AWG |
| Rheem RTEX-24 | 24 | 100.0 | 3 | 33.3 | 40 A | 8 AWG |
| Rheem RTEX-27 | 27 | 112.5 | 3 | 37.5 | 40 A | 8 AWG |
| Rheem RTEX-36 | 36 | 150.0 | 4 | 37.5 | 40 A | 8 AWG |
| Stiebel Eltron Tempra 12 | 12 | 50.0 | 1 | 50.0 | 50 A | 8 AWG |
| Stiebel Eltron Tempra 15 | 14.4 | 60.0 | 2 | 30.0 | 30 A | 10 AWG |
| Stiebel Eltron Tempra 20 | 19.2 | 80.0 | 2 | 40.0 | 40 A | 8 AWG |
| Stiebel Eltron Tempra 24 | 24 | 100.0 | 2 | 50.0 | 50 A | 8 AWG |
| Stiebel Eltron Tempra 29 | 28.8 | 120.0 | 3 | 40.0 | 40 A | 8 AWG |
| Stiebel Eltron Tempra 36 | 36 | 150.0 | 3 | 50.0 | 50 A | 8 AWG |
Every breaker here is double-pole, one per circuit, and each circuit runs to its own terminal on the heater. Rheem recommends at least a 150 A panel for the RTEX-18, 200 A for the RTEX-24 and RTEX-27, and 300 A for the RTEX-36, and notes that a panel upgrade is often needed.
How to work out the amps
Amps = watts ÷ volts. A 27 kW heater is 27,000 W; at 240 V that is 112.5 A. Spread over Rheem’s 3 circuits it is 37.5 A each, on a 40 A breaker.
The size you need comes from your hot water demand and climate. One shower and a kitchen tap, 3.6 GPM at 120°F, takes a 27 kW unit and 113 A where winter water comes in at 70°F, and 36 kW and 150 A where it comes in at 58°F. Colder than that and one electric unit cannot keep up. The electric tankless calculator works it out for your fixtures.
Does the 125% rule apply?
Not in the way it does for a tank. NEC 422.13 treats a fixed storage water heater of 120 gallons or less as a continuous load, so its breaker and wire must be rated at 125% of the heater. That section is written for storage heaters; a tankless heater has no tank. Its breakers are the ones it was tested and listed with, and NEC 110.3(B) requires listed equipment to be installed according to its instructions.
The table shows the result: Rheem’s RTEX-18 carries 37.5 A on each 40 A breaker, and the Stiebel Eltron Tempra 24 50.0 A on each 50 A breaker, much closer to the load than 125%. That is why online answers that multiply a tankless heater’s amps by 1.25 come out higher than the manual. Use the manual’s breaker: a larger one no longer protects the wire, and a smaller one trips.
What wire size
The wire must be rated for at least the breaker. Copper ampacity from NEC Table 310.16:
| Wire | NM-B (60°C) | THHN/THWN (75°C) |
|---|---|---|
| 12 AWG | 20 A | 20 A |
| 10 AWG | 30 A | 30 A |
| 8 AWG | 40 A | 50 A |
| 6 AWG | 55 A | 65 A |
| 4 AWG | 70 A | 85 A |
- 40 A circuits take 8 AWG copper in either NM-B cable or THHN.
- 50 A circuits take 8 AWG only as 75°C wire with 75°C terminals, which is what Stiebel Eltron’s sheet specifies. In NM-B cable a 50 A circuit needs 6 AWG.
- 30 A circuits take 10 AWG.
Long runs may need a size up for voltage drop; the manual and your electrician decide that.
On 208 V
Apartments and commercial buildings often have 208 V instead of 240 V. An element’s resistance is fixed, so its power falls with the square of the voltage: a 36 kW heater rated at 240 V gives 27.0 kW at 208 V and draws 130.0 A, 43.3 A per circuit. Stiebel Eltron lists the Tempra 36 at 27 kW and 44 A per circuit on 208 V, on the same 50 A breakers. Expect less hot water, not a smaller breaker.
Electric tank water heaters, for comparison
Here the 125% rule does apply. Divide the element wattage by 240, multiply by 1.25 and round up to the next standard breaker size (NEC 240.6(A)):
| Element | Amps | × 1.25 | Smallest breaker | Copper wire |
|---|---|---|---|---|
| 3,500 W | 14.6 | 18.2 | 20 A | 12 AWG |
| 4,500 W | 18.8 | 23.4 | 25 A | 10 AWG |
| 5,500 W | 22.9 | 28.6 | 30 A | 10 AWG |
A 30 A breaker on 10 AWG copper also covers a 4,500 W tank, since it exceeds the 23.4 A minimum.