What size breaker for a tankless water heater?

The kilowatt rating sets the amps; the manual sets the breakers.

Short answer

Use the breakers in the installation manual. Whole-house electric tankless heaters split their load across two to four 240 V circuits, each on a 40 or 50 A double-pole breaker. Rheem’s 18 kW RTEX-18 draws 75 A and takes 2 × 40 A breakers; a 36 kW unit draws 150 A and takes 4 × 40 A (RTEX-36) or 3 × 50 A (Stiebel Eltron Tempra 36). For the total amps, divide the watts by 240.

Size an electric tankless and its amps

Breakers by model

240 V. Circuits, breakers and wire from the Rheem RTEX spec sheet (TKE-101 rev. 8) and the Stiebel Eltron Tempra engineering specification (rev. 6.2025); amps computed from kW
ModelkWTotal ampsCircuitsAmps per circuitBreaker eachCopper wire
Rheem RTEX-181875.0237.540 A8 AWG
Rheem RTEX-2424100.0333.340 A8 AWG
Rheem RTEX-2727112.5337.540 A8 AWG
Rheem RTEX-3636150.0437.540 A8 AWG
Stiebel Eltron Tempra 121250.0150.050 A8 AWG
Stiebel Eltron Tempra 1514.460.0230.030 A10 AWG
Stiebel Eltron Tempra 2019.280.0240.040 A8 AWG
Stiebel Eltron Tempra 2424100.0250.050 A8 AWG
Stiebel Eltron Tempra 2928.8120.0340.040 A8 AWG
Stiebel Eltron Tempra 3636150.0350.050 A8 AWG

Every breaker here is double-pole, one per circuit, and each circuit runs to its own terminal on the heater. Rheem recommends at least a 150 A panel for the RTEX-18, 200 A for the RTEX-24 and RTEX-27, and 300 A for the RTEX-36, and notes that a panel upgrade is often needed.

How to work out the amps

Amps = watts ÷ volts. A 27 kW heater is 27,000 W; at 240 V that is 112.5 A. Spread over Rheem’s 3 circuits it is 37.5 A each, on a 40 A breaker.

The size you need comes from your hot water demand and climate. One shower and a kitchen tap, 3.6 GPM at 120°F, takes a 27 kW unit and 113 A where winter water comes in at 70°F, and 36 kW and 150 A where it comes in at 58°F. Colder than that and one electric unit cannot keep up. The electric tankless calculator works it out for your fixtures.

Does the 125% rule apply?

Not in the way it does for a tank. NEC 422.13 treats a fixed storage water heater of 120 gallons or less as a continuous load, so its breaker and wire must be rated at 125% of the heater. That section is written for storage heaters; a tankless heater has no tank. Its breakers are the ones it was tested and listed with, and NEC 110.3(B) requires listed equipment to be installed according to its instructions.

The table shows the result: Rheem’s RTEX-18 carries 37.5 A on each 40 A breaker, and the Stiebel Eltron Tempra 24 50.0 A on each 50 A breaker, much closer to the load than 125%. That is why online answers that multiply a tankless heater’s amps by 1.25 come out higher than the manual. Use the manual’s breaker: a larger one no longer protects the wire, and a smaller one trips.

What wire size

The wire must be rated for at least the breaker. Copper ampacity from NEC Table 310.16:

Copper conductors. NM-B cable is limited to the 60°C column; the 75°C column needs 75°C wire and 75°C terminals. NEC 240.4(D) caps 12 and 10 AWG at 20 and 30 A
WireNM-B (60°C)THHN/THWN (75°C)
12 AWG20 A20 A
10 AWG30 A30 A
8 AWG40 A50 A
6 AWG55 A65 A
4 AWG70 A85 A
  • 40 A circuits take 8 AWG copper in either NM-B cable or THHN.
  • 50 A circuits take 8 AWG only as 75°C wire with 75°C terminals, which is what Stiebel Eltron’s sheet specifies. In NM-B cable a 50 A circuit needs 6 AWG.
  • 30 A circuits take 10 AWG.

Long runs may need a size up for voltage drop; the manual and your electrician decide that.

On 208 V

Apartments and commercial buildings often have 208 V instead of 240 V. An element’s resistance is fixed, so its power falls with the square of the voltage: a 36 kW heater rated at 240 V gives 27.0 kW at 208 V and draws 130.0 A, 43.3 A per circuit. Stiebel Eltron lists the Tempra 36 at 27 kW and 44 A per circuit on 208 V, on the same 50 A breakers. Expect less hot water, not a smaller breaker.

Electric tank water heaters, for comparison

Here the 125% rule does apply. Divide the element wattage by 240, multiply by 1.25 and round up to the next standard breaker size (NEC 240.6(A)):

Electric tank water heater, one element on at a time, 240 V
ElementAmps× 1.25Smallest breakerCopper wire
3,500 W14.618.220 A12 AWG
4,500 W18.823.425 A10 AWG
5,500 W22.928.630 A10 AWG

A 30 A breaker on 10 AWG copper also covers a 4,500 W tank, since it exceeds the 23.4 A minimum.

Frequently asked questions

What size breaker for an 18 kW tankless water heater?
Two 40 A double-pole breakers for Rheem’s RTEX-18. It draws 75 A at 240 V, 37.5 A on each circuit.
What size breaker for a 27 kW tankless water heater?
Three 40 A double-pole breakers for Rheem’s RTEX-27, each carrying 37.5 A of its 112.5 A. Rheem recommends a 200 A panel for it.
What size breaker for a 36 kW tankless water heater?
It draws 150 A at 240 V. Rheem’s RTEX-36 takes four 40 A breakers; Stiebel Eltron’s Tempra 36 takes three 50 A. Rheem recommends a 300 A panel.
What size wire for a tankless water heater?
8 AWG copper for each 40 A circuit. For 50 A circuits, 8 AWG copper rated 75°C with 75°C terminals, or 6 AWG in NM-B cable.
How many amps does a tankless water heater draw?
Kilowatts × 1,000 ÷ 240. An 18 kW unit draws 75 A, a 24 kW 100 A, a 27 kW 112.5 A and a 36 kW 150 A.
Is a tankless water heater a continuous load?
NEC 422.13 makes storage water heaters of 120 gallons or less a continuous load, sized at 125%. It does not name tankless heaters, so follow the breaker size in the installation manual.
Can I put an electric tankless on a 100 amp panel?
Rarely. Even the 18 kW RTEX-18 draws 75 A, and Rheem recommends at least a 150 A panel for it. Small point-of-use units are a different matter.
What size breaker for a 4500 watt water heater?
That is a tank heater: 18.8 A × 1.25 = 23.4 A, so at least 25 A. A 30 A breaker on 10 AWG copper is also correct. A 5,500 W element needs 30 A.
What size breaker for a gas tankless water heater?
None of its own size. It needs a 120 V supply for its controls and fan; the Rinnai RU series draws 4 A at most.

Work it out for your own project